HD Pendent and Upright sprinklers are designed for use in light and ordinary hazards. The temperature response is standard response (5mm glass bulb) and quick response (3mm glass bulb). The sprinklers come with compact design, glass bulb type, available in several different finishes and temperature ratings. The pendent sprinklers must be installed in pendent position, and upright sprinklers are to be installed in the upright position. Pendent Recessed Sprinklers are installed with adjustable or non-adjustable Escutcheon plates (also termed as Rosette plates). These are intended to be installed with finished ceilings. Escutcheon plate adjustment provides convenience in Pendent Sprinkler installation in case of areas with finished ceilings or walls
Full DescriptionType | Pendent |
Style | Pendent |
|
|
Bulb Size | Standard Response - 5mm/Quick Response - 3mm |
Temperature Range | 57/68/79/93/141/182 Degree. |
Working Pressure | Max Working Pressure - 175 PSI or 12 Bar |
Finishing | Brass,Chrome Plated,White Painted |
Thread Size | 1/2" BSPT (NPT Optional) |
K Factor | 5.6 US (80 metric) |
Response | Standard and Quick Response |
Bulb | Glass |
Nominal Thread Size | 1/2" BSPT (NPT Optional) |
Sprinkle Type | Pendent |
Intended Use | Fire Safety/Fire Protection. |
Glass Bulb Colour | Orange/Red/Yellow/Green/Blue/Purple |
Deflector | Brass |
Factory Hydrostatic Test | 500 PSI (35 Bar) |
Material | Brass,Chrome Plated |
Temperature Rating | 57 Degree/68 Degree/79 Degree/93 Degree/141 Degree/182 Degree Celsius |